CAN/ULC-536-13 (Canadian Annual Fire Alarm Inspection Standard)
DO’S AND DON’T’S

DEBUNKING THE MYTHS & COMMON MISCONCEPTIONS ABOUT END-OF-LINE TESTING!

By Frank Kurz

Common Myths and Misconceptions:

#1 - I don’t have to test end-of-line resistors.

#2 - I don’t have to test end-of-line power supervision relays.

#3 - End-of-Line resistors don’t have to be mounted on a plate.

#4 - I don't ever have to perform voltage drop tests.

 

Some Battlefield Examples:

Example #1:

IMG_0740a

 

This picture depicts a common installation error for end-of-line resistor terminations (they’re “floating” free inside a Listed enclosure).  What makes this installation unique is the rather interesting way the “installer” decided to use a Mircom terminal strip.  You’ll note the violet and yellow wires are crimped into the connector while the end-of-line resistor is terminated under the screws.  The other resistor (at the end of the second set of violet and yellow wires at the lower right) is terminated in the more “traditional” method  which employs wire nuts.  It’s still wrong!

Example #2:

IMG_0236b

 

This is a Notifier 5000 system.  The Notification Appliance Circuits are the first eight terminals of the common control board.  Terminals 1 & 4 are NAC 1 (IND 1) for Class “B”.  For a Class “A” circuit, terminals 2 & 3 provide the alternate path to the notification appliances.  Terminals 5 & 8 are NAC 2 (IND 2) for Class “B”.  As you can see there’s a resistor across these terminals in addition to the field wiring.  We found the end-of-line plate still mounted in a hallway next to a non-functional bell.

 

INSPECTION STANDARD REQUIREMENTS:

Let's review the relevant sections of CAN/ULC-S536-13 as they apply to end-of-line resistor testing. Section 6.7.11 is entitled CIRCUIT END-OF-LINE DEVICE and it states:

“Shall” is an imperative, folks.  It’s mentioned FOUR times in these clauses.

 

INSTALLATION STANDARD REQUIREMENTS:

Let's review the relevant sections of CAN/ULC-S524-14 as they apply to end-of-line resistor installation requirements. Section 10.1 is entitled END-OF-LINE DEVICES and it states:

Notice how there’s only one “may” in this entire section and it has to do with the location of an end-of-line device connected to a single field device on a circuit.

 

FIRE CODE REQUIREMENTS:

Let's review the British Columbia Fire Code Division “B” Part 6.  Because it's based on the National Fire Code I'm pretty sure the wording and references are good for other provinces.  It is where we'll find:

There’s that pesky little “shall” again.  What do these clauses mean?  Simple!  You are in violation of the Fire Code if you are not testing a fire alarm system’s components properly - IN ACCORDANCE WITH THE STANDARD!

 

DISPELLING THE MYTHS (AND A WARNING FOR TECHNICIANS CONTEMPLATING PRACTICE ON THE DARK SIDE):

End-of-line resistors and power supervision relays are devices employed to supervise the wiring between a fire alarm control panel (or an addressable module) and the connected conventional field devices.  The term “end-of-line” describes not only the device, but where it should be mounted (at the “end” of, or as the last device in, a circuit).  As the “last device”, it’s also the perfect place to perform the voltage drop test required by another Standard, CAN/ULC-S537-13 (Standard for Verification of Fire Alarm Systems).  The annual test likely won’t discover an illegal “T” tap on a conventionally supervised device circuit (the VERIFICATION is supposed to pick that up). 

Making sure all of the Verification documentation is on hand should be part of what you should be doing before you even start your annual inspection.  Our building annual inspection form (available from our FORMS page) actually lists the documentation you should be checking for.  The latest edition of the Fire Alarm Inspection Standard (CAN/ULC-S536:2019) has some significant changes .

Many managers of fire service companies promote (often encourage) the use of “short cuts” (illegal practice) through special incentives which they sometimes offer to their “less savvy” (or equally unethical) technicians.  End-of-line resistor and smoke detector sensitivity testing are usually the first casualties in the battle to stay competitive.  Incentives to circumvent their proper testing could take the form of monetary “bonuses” or verbal accolades (“You’re our STAR tech!”) if you’ve managed to complete the testing in a project faster than the-guy-who-did-it-last-year

Before we “wax poetic” on the lack of ethics required to accept such dubious rewards, let’s take a very quick look at some of the FINE structures established by various jurisdictions across Canada for violations of the published Provincial Fire Code. 

First off, you’ll find this section of the National Fire Code in almost every municipal Fire Bylaw I’ve reviewed:

Section “C” is entitled “Administrative Provisions”.

Clause 2.2.1.1 states:

Clause 2.2.1.2 states:

Fine Schedule (we’ll be adding more as the information is provided):

Province

Jurisdiction

Reference & Fine

British Columbia

Vancouver

Bylaw 8191 Clause 8.3.1.1(1)
Maximum $2000.00 each offence

Surrey

Bylaw 10771 Sentence 37
Maximum $2000.00 each offence

Abbotsford

Bylaw 1514-2006 Part X 10.4(a)
Maximum $10,000.00 each offence

Kamloops

Bylaw 10-37
Section 423 - $250.00
Section 431(a) - $300.00
Section 431(b) - $300.00
Section 431(d) - $300.00
Section 431(h) - $300.00

Alberta

All Municipal Jurisdictions

Alberta Safety Code Act
Maximum $100,000.00 each offence
& criminal conviction

Saskatchewan

Saskatoon

Bylaw 7990 Part IX 44(2)
a) First Offence - $250.00
b) Second Offence - $500.00
c) Third Offence - $500.00 (min)
$10,000.00 (max - indivdual)
$25,000.00 (max - corporation)

Manitoba

City of Thompson

Fee & Fine Schedule
Failure to Maintain - $75.00

Ontario

All Municipal Jurisdictions

Ontario Fire Service Messenger
Fines have been levied that vary from
 $6000.00 - $56,865.00

Quebec

Montreal

Bylaw 12-005 8.
(1) Individual
a) $500 - $1000 first offence
b) $1000 - $2000 subsequent offence
(2) Corporation
a) $1000 - 2000 first offence
b) $2000 - $4000 subsequent offence

Prince Edward Island

Charlottetown

Fire Prevention Bylaw 11.1
Maximum $2000.00 each offence

New Brunswick

Saint John

Bylaw M-34 Section 6
Maximum $5200.00 each offence
(Minimum $2000.00)

Nova Scotia

Halifax

Bylaw F-100 8.1.4.1(1)
Maximum $5000.00 each offence

All Municipal Jurisdictions

Fire Safety Act 2002 44(2)
Maximum $25,000.00 each offence
& six months imprisonment
Where loss of life occurs
Maximum $150,000.00 &
two years imprisonment

Newfoundland/Labrador

TBA

TBA

Yukon Territory

TBA

TBA

Nunavut

TBA

TBA

Northwest Territories

TBA

TBA

 

It is both the duty and the responsibility of every technician engaged in the service, testing, and inspection of a fire alarm system to ensure that what they’re doing complies with the relevant Codes and Standards.  It goes without saying (but I’ll say it anyway) that non-compliance carries with it the possibility of hefty monetary penalties and possible incarceration (which could mean a criminal record).  As the solely appointed “agent” of the Owner, YOU, yes, you (the guy performing the inspection) becomes directly responsible to ensure that the service you provide is above reproach.  Agents of your employer (e.g. service manager, manager) may decide to justify “under-cutting” the competition to get the job by offering the suggestion that the testing is “not required” because no one else is doing it.  There is however, no way you should be accepting responsibility for such substandard work (or cut the corners your employer may suggest) simply because there no way to justify any departure from the Testing Standard.  If what you’re being asked to do (or submit in the way of paperwork) doesn’t comply with the Standard, it is YOU who will bear the ultimate responsibility.  Your signature, after all is said and done, is on the report (and on any of  the tags affixed to the fire protection equipment). 

YOU WILL (EVENTUALLY) GET CAUGHT!

 

TIPS AND RESOURCES:

We review the correct procedure (required by ASTTBC’s Practice Guideline under the heading Preparation) that you should follow prior to performing any life safety equipment testing in this FAQ.

There is additional information regarding the Annual Testing of Fire Protection Equipment located in our FAQS page.

 

Questions?

Call or email us!

 

panel_tl

panel_tr

Points of Interest:
Stir up the Gray Matter with
Nick Markowitz &
Al Colombo

Smoke Detector Cross Listing Information:
ULC Smoke Detector Compatibility Index
(You’ll be prompted to either “save as” or “open” a Microsoft a Microsoft® Excel document. Please read our Terms of Use.)

Technical Forums:
Our forums are LIVE and guaranteed SPAM FREE!

Library:
Check out some really useful Technical Guides and Manuals in our Library!

Links Page:
Our Links page makes finding the information you need really easy!


If you've found our site useful, you may wish to consider supporting our efforts by becoming an Associate Member.

Paypal

Building Annual Inspection Form
(Includes CAN/ULC-S536-04
Appendix E - Amended for
CAN/ULC-S524-06
)

MS Word.doc           PDF

In Memoriam
G. Richard (Rich) Morris
Celebrating a truly
remarkable life!

CFAA’s Tribute
SCC’s Tribute
ULC’s Tribute

In Memoriam
David Sylvester
CFAA Legend, Educator,
and Friend!

CFAA’s Tribute

panel_bl

panel_br

The Fire Technicians Network

+1 (888) 340-3473

“We are not a professional union, but together, we are a union of professionals!”

Social MediaFTN Twitter FeedFTN Facebook FeedFTN LinkedIN FeedTechnical RSS FeedSkype for Business

What we’re all about!
We are not affiliated with ASTTBC, CFAA, CANASA, NFPA, NAFED, or NICET (although we encourage you to explore and objectively evaluate the benefits associated with supporting their individual efforts).  Membership in the Fire Technicians Network is entirely voluntary.  Are you up to the challenge of demonstrating your commitment to public safety and the highest standard of professional practice?

Social MediaFTN Twitter FeedFTN Facebook FeedFTN LinkedIN FeedTechnical RSS FeedSkype for Business

Copyright © 2007 - 2021 The Fire Technicians Network.  All Rights Reserved