Smoke Alarm RECALL (July 2009):
Kidde has announced a voluntary recall of their Model PI 2000CA dual sensor smoke alarms. Apparently an electro-static discharge can adversely affect the detector. Affected units were manufactured between January 1, 2009 and May 4, 2009. You can view all the details (and what you must do) here.
Fire Extinguisher RECALL (March 2009):
Affects Kidde XL Fire Extinguishers manufactured betwen October 2007 and April 2008 with model numbers FX210R and E-340-3. The extinguisher can lose pressure which could put the end-user at risk. Consumers are urged to check the pressure gauge to ensure it is still in the "green" range. They are also urged to contact Kidde Customer Support to verify that their extinguisher serial number does not fall within the range of this recall. The Customer Support number is listed below.
Commercial Fire Extinguisher RECALL (July 2005):
Affects Kidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000. The nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards creating a safety hazard to fire extinguisher service personnel and consumers. DO NOT SERVICE THESE EXTINGUISHERS! More details concerning this recall and the replacement program can be found here.
Firex Smoke Alarm/Carbon Monoxide Detector RECALL:
Affects Maple Chase Company products that include Firex branded model 10000 and 12000 series smoke alarms and carbon monoxide detectors. You may view additional information here.
Chemtronics 500 & 600 series Heat Detectors BULLETIN:
Kidde/Fenwal have issued a bulletin regarding the terminal strips located on the bottom of the affected detectors. Apparently some units were manufactured with "out of tolerance" rivets which may cause the entire terminal assembly to separate from the body of the detector. On supervised fire alarm circuits this would NOT cause a "trouble" signal as the terminal strip still provides a positive connection, however, the unit will fail to register an alarm condition. You can view additional information (including the corrective action you must take) here.
Technical Support: +1 (888) 345-4407
Bulletins, Recalls, & Technical Service Notes:
+1 (888) 340-3473
“We are not a professional union, but together, we are a union of professionals!”
What we’re all about!
We are not affiliated with ASTTBC, CFAA, CANASA, NFPA, NAFED, or NICET (although we encourage you to explore and objectively evaluate the benefits associated with supporting their individual efforts). Membership in the Fire Technicians Network is entirely voluntary. Are you up to the challenge of demonstrating your commitment to public safety and the highest standard of professional practice?
Copyright © 2007 - 2020 The Fire Technicians Network. All Rights Reserved